Search:

KNX Power Supply 640mA

Product Code: LXA-164-30V

The iluxusdesign KNX power supply generates a voltage of DC 30V and has an additional auxiliary voltage output. The integrated throttle decouples the KNX bus line from the 30 V DC auxiliary voltage. Both outputs are overload and short circuit proof. Any desired load distribution across the outputs is possible up to a maximum of 640 mA. The LED status shows the device status and overload. Resetting is done by pressing RESET button on the front of the device.

Product Characteristics

  • 640 mA output current
  • Operating AC 150V – 275V @50-60 Hz
  • 2 Power Outputs: Output 1: Integrated KNX Choke (DC 30V, SELV) Output 2: External Auxiliary Supply Output (30V, SELV)
  • Short Circuit Protection for both outputs
  • Overload Protection for both outputs
  • 3 LED Indicators:
    Left LED (Green): Power
    Middle LED (Red): Overload or Short Circuit (Iout > 900 mA, LED is ON; Otherwise, LED is OFF)
    Right LED (Red): Reset

Please Read Carefully Before First Use

  • The device may only be installed and put into operation by a qualified electrician or authorized personnel
  • For planning and construction of electric installations the corresponding specifications, guidelines and regulations that must be observed in the respective country
  • For mounting use an appropriate equipment according to IEC60715
  • Installation only in distribution boards and enclosed housings
  • Installation only on a 35 mm DIN rail (Th35)
  • Contact protection must be provided through the control cabinet
  • Connect the KNX bus line as for common KNX bus connections with a KNX TP bus cable, to be stripped and plugged into a KNX TP connector
  • Do not damage electrical insulations when connecting
  • The housing must not be opened
  • Protect the device from moisture, dirt and damage
  • The device needs no maintenance
  • In the case of damage no repairs may be carried out by unauthorized personnel

Connection Diagram

Scale Drawing

Technical Data

Type of protectionIP 20EN 60529
Safety classııEN 60664
Power SupplyMains VoltageAC 230V ±15 % @ 50 Hz
Leakage Loss (Open Circuit)1,2 W
Leakage Loss (Normal)3,4 W
Power Consumption (Normal)23 W
Power Consumption (Max. Overload)42 W
Power OutputKNX Output Voltage28 ... 31 VDC (SELV)
AUX Output Voltage28 ... 31 VDC (SELV)
Rated Current640 mA
Maximum Current (Total Output)1,2 A
Mains failure bridging time> 100 ms
Efficiency at nominal load81 %
With in Space Unit4 Modules (1 Module = 18 mm)
ConnectionsScrew Terminals0,3 - 2,5 mm²
Max. Torque0,4 Nm
KNX Connection Bus Terminal0,8 mm² Ø, solid core
Installation35mm DIN Rail
Operating ElementReset ButtonReset at the EIB/KNX Output
Left LED (Green)Output Voltage is OK
Middle LED (Red)Overload or Short Circuit
Right LED (Red)Reset
Temperature RangeOperation(-5°C ... +45°C)
Storage(-20°C ... +70°C)
HumidityMaximum air humidity5% ... 93% (non consendation)
FlammabilityNon-flammable product
DimensionsL:70 W:90 H:65 mm
Weight206 gr
StandartsEN50491-5-1 / -2 / -3, EN50581
EN61000-6-2 / -3
EN61558-1 / -2-6
CertificationKNX Certified